Window AC BTU Calculator & ENERGY STAR Room Chart
Look up a room-cooling starting point using the published ENERGY STAR floor-area bands, then apply its stated adjustments.
Calculate your planning estimate
Updates as you type. Every unit is labelled. Change example values to your design data.
Results
Rounded for display. Estimates are not equipment specifications.
Formula & assumptions
Adjusted BTU/h = chart base × sun/shade factor + 600 × max(occupants − 2, 0) + kitchen allowance (4,000 if selected).
All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.
Published room-cooling chart
Source: ENERGY STAR Room Air Conditioners, checked 24 November 2026. Its capacities are based on an 8-foot ceiling. This is a room-air-conditioner screening chart, not a whole-home load calculation or a rule for ducted systems.
| Area to cool (ft²) | Base cooling (BTU/h) |
|---|---|
| 100–<150 | 5,000 |
| 150–<250 | 6,000 |
| 250–<300 | 7,000 |
| 300–<350 | 8,000 |
| 350–<400 | 9,000 |
| 400–<450 | 10,000 |
| 450–<550 | 12,000 |
| 550–<700 | 14,000 |
| 700–<1,000 | 18,000 |
| 1,000–<1,200 | 21,000 |
| 1,200–<1,400 | 23,000 |
| 1,400–<1,500 | 24,000 |
| 1,500–<2,000 | 30,000 |
| 2,000–2,500 | 34,000 |
Boundary convention used here: each lower edge is included; the upper edge is excluded, except 2,500 ft² is included in the last row. Thus exactly 300 ft² uses the 300–350 row. The chart is not extrapolated below 100 or above 2,500 ft².
Adjustments and example
The source says to reduce capacity by 10% for heavy shade or increase it by 10% for a very sunny room, add 600 BTU/h for each regular occupant beyond two and add 4,000 BTU/h for a kitchen. We apply the exposure adjustment to the base first, then add occupants and kitchen. At 300 ft², three occupants and very sunny exposure, the calculation is 8,000 × 1.10 + 600 = 9,400 BTU/h.
When not to rely on this chart
High ceilings, unusual glazing, major heat-producing equipment, severe climate conditions and rooms open to other spaces need a closer load assessment. No numeric ceiling-height factor is invented here. Oversizing can reduce humidity control. Use actual rated performance at your conditions rather than blindly rounding to the largest unit.
Questions about this tool
Does the result include a high-ceiling correction?
No. ENERGY STAR bases the table on 8-foot ceilings but does not publish a numeric correction on the cited page.
Why does 300 ft² produce 8,000 rather than 7,000 BTU/h?
We consistently assign exact shared boundaries to the next area band, and display this convention beside the table.
Sources & method references
Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.
Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.