AC Tonnage Calculator from Sensible & Latent Loads
Combine a sensible load and a moisture-removal load, then express the total in refrigeration tons. No assumed tons-per-square-foot rule.
Calculate your planning estimate
Updates as you type. Every unit is labelled. Change example values to your design data.
Results
Rounded for display. Estimates are not equipment specifications.
Formula & assumptions
Total cooling = sensible + latent. Refrigeration tons = total BTU/h ÷ 12,000. SHR = sensible ÷ total.
All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.
Read the load report correctly
Sensible cooling lowers air temperature. Latent cooling removes moisture. Use the separate sensible and latent lines of the same design report and at the same conditions. If you only have a total load, enter that total as sensible and zero as latent to convert units, but do not treat the resulting SHR as measured performance.
Example and conversion reference
A 24,000 BTU/h sensible load plus 6,000 BTU/h latent load totals 30,000 BTU/h: 2.5 refrigeration tons and about 8.79 kW of thermal cooling. The load SHR is 0.80. Thermal kW is heat removed, not the electrical input at the meter.
| Cooling tons | BTU/h | Thermal kW |
|---|---|---|
| 1 | 12,000 | 3.517 |
| 1.5 | 18,000 | 5.275 |
| 2 | 24,000 | 7.034 |
| 2.5 | 30,000 | 8.792 |
| 3 | 36,000 | 10.551 |
Nominal capacity is not a design guarantee
A nominal rating is measured at stated test conditions. Actual sensible and total capacity depend on indoor wet-bulb temperature, outdoor temperature and airflow. A designer must check equipment performance tables against both load components and confirm acceptable part-load moisture control. This arithmetic is not a substitute for ACCA Manual J or equipment selection.
Questions about this tool
Does 2.5 tons mean a 2.5-ton label always works?
No. The equipment must meet the actual sensible and latent loads at your design conditions.
Is one cooling ton a weight?
No. A refrigeration ton is a heat-transfer rate of 12,000 BTU per hour, not a mass or a fuel quantity.
Sources & method references
Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.
Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.