Room BTU Calculator for Heating from UA & Airflow

For room-level heating, use an envelope heat-loss coefficient rather than a generic area multiplier. For a window-unit cooling chart, use the separate window AC tool.

Calculate your planning estimate

Updates as you type. Every unit is labelled. Change example values to your design data.

Allowed input: 0.01 to 1000000. These are calculator bounds, not code limits.
Re-enter area when switching units; 1 m² = 10.7639 ft².
Sum exterior surface area ÷ whole-assembly R-value for this room. Excludes outdoor air. Allowed input: 0 to 10000. These are calculator bounds, not code limits.
Allowed input: -100 to 200. These are calculator bounds, not code limits.
Allowed input: -150 to 200. These are calculator bounds, not code limits.
Both indoor and outdoor values use this selection; re-enter values after switching.
Allowed input: 0 to 10000. These are calculator bounds, not code limits.

Results

Rounded for display. Estimates are not equipment specifications.

Formula & assumptions

Room BTU/h = [fabric UA + 1.08 × outdoor CFM] × max(inside − outside, 0) in °F.

All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.

How to obtain room UA

UA is the sum of U × area for the room’s exposed assemblies. In US units U = 1/R, so a 100 ft² wall at whole-assembly R-10 contributes 10 BTU/h·°F. Add the net wall, glazing, exposed ceiling and other boundary terms. Do not add an internal partition facing an equally warm room as if it faced the outdoor design temperature.

Floor area is a comparison, not the engine

The room floor area is used only to display the calculated BTU/h per ft². It does not create the load. Keeping UA and airflow fixed while changing floor area should leave total loss unchanged. This distinction is useful when comparing an exposed corner bedroom with an inner room of the same size.

A single-room example

A room with fabric UA 35 and 15 CFM outdoor air at 70°F indoors and 10°F outdoors loses (35 + 1.08 × 15) × 60 = 3,072 BTU/h. At 200 ft², that works out to 15.36 BTU/h per ft². This ratio is an output of the example, not a transferable sizing rule.

No solar gains, room-by-room cooling, duct loss, air-transfer paths or balancing design are calculated here. For emitters or air handlers, a professional still needs distribution and equipment performance information.

Questions about this tool

Is this room cooling BTU?

No. This page estimates winter heating loss. The window AC page applies an official room-cooling chart.

What happens if I switch to m²?

Enter the equivalent floor area yourself. The UA field remains in US heat-loss-coefficient units as its label states.

Sources & method references

Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.

Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.