UK Boiler Size Calculator: Heating, Cylinder & DHW kW
Keep room heating demand separate from domestic hot water. A combi’s hot-water output and a system boiler’s cylinder reheat requirement are different design questions.
Calculate your planning estimate
Updates as you type. Every unit is labelled. Change example values to your design data.
Results
Rounded for display. Estimates are not equipment specifications.
Formula & assumptions
Cylinder kW ≈ litres × 4.186 × temperature rise ÷ (3,600 × recovery hours). Instantaneous kW ≈ L/min × 4.186 × rise ÷ 60.
All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.
Three loads, not one bedroom multiplier
Start with a room-by-room design heat loss for space heating. A cylinder reheat calculation estimates the average heat rate needed to raise a known water volume by a chosen temperature rise in an allowed time. An instantaneous calculation estimates hot-water output at a continuous draw. None of these is a count of bedrooms or radiators.
Example: why hot-water labels can be larger
Reheating 150 litres from 10°C to 60°C in one hour needs about 8.72 kW of average useful heat, ignoring losses. A continuous 10 litres/minute at the same 50 K rise needs about 34.88 kW. That high instantaneous figure does not mean the home’s 8 kW space-heating loss suddenly becomes 34.88 kW.
Priority versus simultaneous operation
The tool displays max(space load, average reheat load) as an arithmetic lower bound for non-simultaneous priority operation, and their sum for simultaneous operation. Priority means room heating is interrupted during hot-water recovery: the lower-bound number alone does not prove acceptable recovery, comfort or control behavior. Cylinder coil transfer capability and boiler modulation can be decisive.
Water properties are approximated as 1 kg per litre and 4.186 kJ/kgK. Standing losses, pipe losses, mixing, flow-pressure limits, coil ratings and safety provisions are outside the arithmetic. An installer must verify the design and suitable minimum output. The entered target water temperature is not a public-health or anti-scald recommendation.
Questions about this tool
Should I add combi DHW output to space heat loss?
Not automatically. Many systems prioritize hot water. The correct selection depends on controls, flow demand and acceptable interruption, not simply adding every rating.
Does the cylinder result guarantee the requested reheat time?
No. The cylinder coil, primary flow temperature, controls and actual boiler output must support that heat transfer rate.
Sources & method references
Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.
Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.