Heating BTU Calculator: Fabric & Air-Exchange Loss

Explore how an exterior assembly and outdoor-air exchange contribute to a winter heat loss. This is a transparent first-pass subtotal, not a whole-house certification.

Calculate your planning estimate

Updates as you type. Every unit is labelled. Change example values to your design data.

Allowed input: 0 to 1000000. These are calculator bounds, not code limits.
Use assembly R, including thermal bridges, not insulation-batt R alone. Allowed input: 0.01 to 200. These are calculator bounds, not code limits.
Allowed input: -100 to 200. These are calculator bounds, not code limits.
Allowed input: -150 to 200. These are calculator bounds, not code limits.
Both indoor and outdoor values use this selection; re-enter values after switching.
Use a design estimate for infiltration + mechanical outdoor air; do not enter recirculating supply airflow. Allowed input: 0 to 10000. These are calculator bounds, not code limits.

Results

Rounded for display. Estimates are not equipment specifications.

Formula & assumptions

Fabric BTU/h = area × ΔT°F ÷ R. Air-exchange BTU/h ≈ 1.08 × CFM × ΔT°F.

All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.

Enter one assembly or a defensible effective R-value

Use net surface area exposed to the design condition, not floor area by default. Subtract windows and doors if they are being calculated separately. The R-value should describe the complete assembly. Combining unlike walls, windows and roofs under a guessed single R-value can seriously understate loss; use the component estimator for separate assemblies.

Worked example

With 1,200 ft² at R-15 and a 60°F difference, fabric loss is 4,800 BTU/h. At 80 CFM, the air-exchange term is 5,184 BTU/h, giving a subtotal of 9,984 BTU/h. These are deliberately illustrative assumptions, not a suggested load for a 1,200 ft² house.

What the estimate leaves out

The 1.08 factor approximates standard sea-level air density × specific heat × 60 minutes. It changes with air conditions and altitude. This tool does not calculate leakage from a blower-door result, heat recovery, ground coupling, duct loss or a warm-up allowance. It also does not calculate cooling or moisture load. If outside is as warm as indoors, winter loss is reported as zero rather than a negative equipment size.

Questions about this tool

Is the R-value metric RSI?

No. Enter US R-value in h·ft²·°F/BTU. Use the UK heat-loss page for U-values in W/m²K.

Can I use supply fan CFM?

No. Outdoor air loss uses outdoor-air exchange, not all the air circulating through the system.

Sources & method references

Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.

Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.