Home / Heat Pump Size Calculator
Independent tools · Transparent assumptions

Heat Pump Size Calculator: Cold-Weather Output & Backup

Compare a candidate heat pump’s available winter output with a known heating load, while keeping the summer cooling requirement visible.

Calculate your planning estimate

Updates as you type. Every unit is labelled. Change example values to your design data.

Allowed input: 0 to 1000000. These are calculator bounds, not code limits.
Allowed input: 0 to 1000000. These are calculator bounds, not code limits.
Changing units changes how the number is interpreted; enter the equivalent value yourself.
Example only. Use extended performance data at design outdoor and indoor conditions. Allowed input: 1 to 150. These are calculator bounds, not code limits.
Allowed input: 0 to 1000000. These are calculator bounds, not code limits.

Results

Rounded for display. Estimates are not equipment specifications.

Formula & assumptions

Winter output = candidate nominal × retained fraction. Backup gap = max(heating load − winter output, 0). Heating-only nominal equivalent = load ÷ retained fraction.

All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.

Follow delivered capacity, not electrical input

Heating output and electrical consumption are different quantities. A coefficient of performance describes output divided by electrical input; it is not the same as the percentage of nominal heating capacity retained in cold weather. This tool uses the capacity ratio only. Both candidate nominal and design load must use the selected thermal units.

Cold-weather example

With a 30,000 BTU/h heating load, a 36,000 BTU/h candidate and a 75% retained-capacity assumption, available heat is 27,000 BTU/h. The arithmetic shortfall is 3,000 BTU/h. Dividing the load by 0.75 gives a heating-only nominal-equivalent target of 40,000 BTU/h. The separate 24,000 BTU/h cooling requirement is not silently converted into that heating target.

A backup gap is not an electrical circuit design

Defrost, lockout settings, recovery, distribution losses and the chosen backup strategy may change delivered comfort. An installer must check low-ambient capacity and controls, seasonal operation and electrical requirements. Selecting for winter alone may oversize summer cooling; modulation and humidity control matter. Obtain an ACCA Manual J calculation and model-specific selection rather than treating this screen as a final schedule.

Questions about this tool

Does the retained percentage mean COP?

No. It is available heating capacity divided by nominal heating capacity, not efficiency.

Does zero backup gap prove no auxiliary heat is needed?

No. It only closes the entered steady-state arithmetic gap; defrost, recovery and operating limits remain outside this tool.

Sources & method references

Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.

Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.