Duct CFM Chart: Round Diameter, Velocity & Heating Airflow
Look up airflow at an explicitly chosen velocity, or calculate it from an inside diameter. Table cells are geometry, not maximum duct capacity ratings.
Calculate your planning estimate
Updates as you type. Every unit is labelled. Change example values to your design data.
Results
Rounded for display. Estimates are not equipment specifications.
Formula & assumptions
Round CFM = π × (diameter in feet)² ÷ 4 × FPM. Separate heating CFM ≈ BTU/h ÷ (1.08 × ΔT°F).
All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.
Round duct airflow reference
All values below are rounded CFM. The columns are selected comparison velocities, not published code limits. Use inside clear diameter. Real delivered flow depends on system resistance and the blower operating point.
| Inside diameter | 400 FPM | 600 FPM | 800 FPM |
|---|---|---|---|
| 4 in | 35 | 52 | 70 |
| 5 in | 55 | 82 | 109 |
| 6 in | 79 | 118 | 157 |
| 7 in | 107 | 160 | 214 |
| 8 in | 140 | 209 | 279 |
| 9 in | 177 | 265 | 353 |
| 10 in | 218 | 327 | 436 |
| 12 in | 314 | 471 | 628 |
| 14 in | 428 | 641 | 855 |
| 16 in | 559 | 838 | 1117 |
| 18 in | 707 | 1060 | 1414 |
Why one diameter has no single CFM rating
An 8-inch round duct has a free area of about 0.3491 ft². At 600 FPM that carries about 209 CFM; at 400 FPM it carries about 140 CFM. Neither number proves a duct is adequately sized. Pressure loss, length, fittings, terminal sound and the available fan pressure still need checking.
The sensible-heating airflow check
For 20,000 BTU/h and a 40°F air temperature rise, the standard-air approximation gives about 463 CFM. This is a separate energy-balance calculation, not a prediction that the entered diameter will carry it. The 1.08 coefficient assumes approximate sea-level standard air. It is not appropriate for a total cooling load with latent moisture removal, and it changes at altitude.
Questions about this tool
Can I use these cells as maximum allowed airflow?
No. They are calculated airflow at stated velocity only, not code limits or a pressure-loss rating.
Why are the two live airflow results different?
One uses diameter and velocity; the other uses sensible heat and air temperature rise. They answer different questions and are not automatically balanced.
Sources & method references
- ACCA — Manual D residential duct systems
- ACCA — Manual J residential load calculation
- Engineering ToolBox — sensible heating and cooling equations
Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.
Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.