Home / UK ASHP Size Estimator
Independent tools · Transparent assumptions

UK ASHP Size Estimator: Design Output, Capacity & COP

Screen an air-source heat pump against the surveyed heat loss at the intended outdoor and flow temperatures. Capacity retention is not efficiency.

Calculate your planning estimate

Updates as you type. Every unit is labelled. Change example values to your design data.

Allowed input: 0 to 200. These are calculator bounds, not code limits.
Illustrative only. Derive from manufacturer data at the required outdoor and leaving-water temperatures. Allowed input: 1 to 150. These are calculator bounds, not code limits.
Allowed input: 0 to 200. These are calculator bounds, not code limits.
Example only; not a seasonal performance promise. Excludes backup and ancillary electricity below. Allowed input: 0.1 to 15. These are calculator bounds, not code limits.

Results

Rounded for display. Estimates are not equipment specifications.

Formula & assumptions

Design output = nominal × capacity fraction. Nominal-equivalent target = heat loss ÷ fraction. Heat gap = max(loss − design output, 0). Compressor input ≈ supplied heat ÷ COP.

All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.

Use the right performance point

An ASHP’s output varies with outdoor temperature and the required leaving-water temperature. Obtain a room-by-room heat-loss calculation and performance data for the proposed system. A nominal kW label measured under different conditions is not sufficient to establish design capacity.

Capacity and efficiency are different

An 80% capacity ratio means a unit supplies 0.8 times its nominal heat output at the entered condition. COP 3 means three units of heat output per unit of electrical input at that point. The calculator never uses COP as a capacity derating factor. A seasonal performance figure is not necessarily the design-point COP.

Worked example

For an 8 kW space heat loss, a 10 kW nominal unit retaining 80% gives 8 kW at the entered condition, closing the simple steady-state gap. At COP 3, compressor input for that delivered heat is about 2.67 kW. This excludes circulation pumps, controls, defrost effects not already reflected in data and any backup-heater electricity. It is not a running-cost or electrical-supply design.

From a capacity screen to a UK design

Check emitter output at the chosen flow temperature, hydraulic design, minimum modulation, hot-water recovery strategy, defrost and controls. The room heat-loss tool and radiator correction tool help explain those constraints, but neither is an MCS survey. Final selection should follow a competent BS EN 12831-based design and current MCS requirements where applicable. This site does not establish grant eligibility or recommend a named product.

Questions about this tool

Should the capacity percentage and COP be the same number?

No. They describe different physical relationships: output relative to nominal, and output relative to electrical input.

Is the electrical result the whole installation demand?

No. It estimates compressor input for the portion of the entered load served by the candidate only. Backup, pumps and other loads are not included.

Sources & method references

Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.

Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.