Duct Size Calculator by CFM & Air Velocity
Convert a design airflow and chosen velocity into free duct area. Useful for an initial space check before pressure-loss and noise design.
Calculate your planning estimate
Updates as you type. Every unit is labelled. Change example values to your design data.
Results
Rounded for display. Estimates are not equipment specifications.
Formula & assumptions
Free area (ft²) = CFM ÷ FPM. Round diameter (in) = 12 × √(4 × area ÷ π). Rectangle height = area × 144 ÷ width.
All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.
What this tool does — and does not do
At 400 CFM and 700 FPM, the required free area is 0.5714 ft², or 82.29 in². The unrounded round diameter is about 10.24 inches; a 12-inch-wide rectangle would need about 6.86 inches free height. These are geometric results before choosing manufactured sizes, liner thickness, pressure loss or acoustic constraints.
Velocity is only one constraint
A complete duct design also checks available external static pressure, filters, coils, fittings, total effective length, balancing devices, terminals and sound. Rectangular and round ducts with equal area do not have equal friction performance. Flexible duct compression and sag can increase resistance substantially. ACCA Manual D covers residential duct design; this page is not a Manual D implementation or a digital friction slide rule.
Use free inside dimensions
The air sees the clear internal cross-section, not outside sheet-metal dimensions or framing openings. Allow for internal liner if present. Choosing a larger area reduces velocity for the same airflow, but fitting geometry and blower operation still matter. No universal “safe CFM” is assigned to a diameter here, and no uncited design velocity band is presented as a mandatory standard.
Questions about this tool
Does this calculate friction in inches water column per 100 feet?
No. It uses the continuity equation only. A friction-rate or static-pressure design requires additional inputs and a full design method.
Are equal-area round and rectangular sizes equivalent?
Only in free area and mean velocity. Their perimeter, hydraulic behavior and pressure loss differ.
Sources & method references
Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.
Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.