Home / UK Heat Loss Calculator
Independent tools · Transparent assumptions

UK Heat Loss Calculator: Fabric, Ventilation & kW

Add fabric and air-exchange losses using metric U-values. Use the result to discuss room heat demand, not to claim a BS EN 12831 design or an MCS survey.

Calculate your planning estimate

Updates as you type. Every unit is labelled. Change example values to your design data.

Allowed input: 0 to 1000000. These are calculator bounds, not code limits.
Allowed input: 0 to 10. These are calculator bounds, not code limits.
Allowed input: 0 to 1000000. These are calculator bounds, not code limits.
Allowed input: 0 to 10. These are calculator bounds, not code limits.
Allowed input: 0 to 1000000. These are calculator bounds, not code limits.
Allowed input: 0 to 10. These are calculator bounds, not code limits.
Allowed input: 0 to 1000000. These are calculator bounds, not code limits.
Allowed input: 0 to 10. These are calculator bounds, not code limits.
Allowed input: 0 to 1000000. These are calculator bounds, not code limits.
Illustrative only; use surveyed/design ventilation and infiltration, not a universal room allowance. Allowed input: 0 to 20. These are calculator bounds, not code limits.
Allowed input: -50 to 100. These are calculator bounds, not code limits.
−3°C is an example, not a UK-wide design temperature. Allowed input: -80 to 100. These are calculator bounds, not code limits.

Results

Rounded for display. Estimates are not equipment specifications.

Formula & assumptions

Fabric W = Σ(U × net area) × ΔT. Air-exchange W ≈ 0.33 × volume(m³) × ACH × ΔT(K).

All defaults are illustrative unless identified as a published chart value. Unit selectors reinterpret values; re-enter equivalent numbers after switching.

Enter measured construction, not a building-age guess

U-values describe whole elements in W/m²K. Use measured dimensions and documented construction values; the defaults simply demonstrate the calculation. Subtract openings from opaque wall area. If an element faces a heated neighbour rather than outdoors, its temperature difference may be much smaller and this one-temperature worksheet may not suit it.

A metric example

The default fabric coefficient is 21.2 W/K. At 21°C indoors and −3°C outdoors, fabric loss is 508.8 W. Air exchange adds 0.33 × 48 × 0.5 × 24 = 190.08 W. Total simplified loss is 698.88 W, or about 0.70 kW. The 0.33 coefficient approximates air density × specific heat divided by 3,600.

Boundaries of the model

This calculation applies the same outdoor temperature difference to every entered element. Ground floors need more careful treatment; party walls, unheated spaces, thermal bridges, ventilation heat recovery, exposure and warm-up are not modeled. The default outdoor temperature and air-change rate are not official regional design values.

From a worksheet to a design

Use an appropriate room-by-room BS EN 12831 calculation and current UK design guidance for final emitter, boiler or ASHP selection. A heat pump installation may require an MCS-compliant heat-loss survey. This simplified tool does not establish compliance, grant eligibility or suitability of an existing distribution system.

Questions about this tool

Can I enter insulation R-value here?

No. The tool takes whole-element metric U-values in W/m²K. Do not enter a US R-value in a U-value field.

Does this include ground-floor and thermal-bridge calculations?

No. Floor loss is a simplified U × area × outdoor difference term, and thermal bridges require separate assessment.

Sources & method references

Reviewed 24 November 2026. References explain methods and limitations; citation does not imply approval or affiliation.

Planning estimates only. Verify dimensions, units, design conditions and manufacturer performance. These tools do not replace ACCA Manual J / Manual D, BS EN 12831, an MCS survey or a qualified system design. Defaults are examples, not industry requirements. HeatCool Lookup is an independent reference site.